TS-1400

From embeddedTS Manuals
Revision as of 23:26, 13 March 2013 by Mark (talk | contribs)
TS-1400
TS-1400.jpg
Released March 2013
Product Page
Documentation
FTP Path
Relays
External Interfaces
2x RJ45 Modbus
Power Requirements
12-24V
Operates around ??
Operating Temperature
Cold -40C
Hot 85C
Mechanical
140mm x 102mm
Height 35mm (approx without baseboard)
Weight 167

Overview

The TS-1700 is a modbus peripheral device which brings out 8 DIO, or 8 one wire temperature sensors.

Getting Started

Power Requirements

Features

TS Modbus Support

When using all Technologic Systems Modbus devices we include functionality to create an arbitrary chain of stock peripherals to automatically enumerate all connected devices, configure them, and generate an I/O map of all connected devices.

TS Modbus Autoconfiguration

The autoconfiguration works by using the optional mode pin on the RJ45 connector as designated in the MODBUS-2W standard. Technologic Systems uses this to indicate if it is a TS device. If it is asserted (low) to a TS device, then it will allow access to the #Holding Registers at address 0xf7.

This will identify the TS Modbus device model, set the first device in the chain to the user specified slave address (default is 0x10), and assert the mode line to the next port to enumerate the next device. The next device address is incremented by 1, and the process is repeated until no slave responds to a read query (timeout)indicats that no additional devices are connected to the bus chain. At this point the last device in the chain is configured to enable bus termination on the RS485 link, and all devices have their bit rates set to the user selected bit rate (default is 9600).

Register Interface

Holding Registers

The holding registers include various settings such as the configurable Modbus Address, termination enable, and more. These settings are common to all of our Modbus peripherals, and are stored in flash to persist between power cycles.

The Modbus protocol supports 64K

Address (hex) Address (dec) Access Description Example Values
0x70 112 Read/Write Modbus Mode 0 = ASCII, 1 = RTU
0x71 113 Read/Write RS485 Bus Termination Enable 0 = No termination, 1 = enable termination
0x72 114 Read/Write Modbus Device Address 0-65535
0x73 115 Read/Write Modbus baud rate Baud Rate
0x74 116 Read Only Unit Model TS-1700
0x75 117 Read Only Verilog Version 1
0x76 118 Read Only ZPU Version 1
0x77 119 Read Only Power Supply in millivolts 24000
0x78 120 Read Only Internal Temperature in 1/100th degree Celsius 22000
0x79 121 Read Only Reserved N/A
0x7a 122 Read Only Reserved N/A
0x7b 123 Read Only Reserved N/A
0x7c 124 Read Only Reserved N/A
0x7d 125 Read/Write Write value 0xfeed to make holding registers persistent N/A

Operating Registers

Baud Rate

The TS-1400 supports 15 speeds:

Value Communication Bit Rate Maximum CAT5 Cable Length
0 300 1200 meters
1 600 1200 meters
2 1200 1200 meters
3 2400 1200 meters
4 4800 1200 meters
5 9600 1200 meters
6 19.2K 1200 meters
7 38.4K 1200 meters
8 57.6K 1200 meters
9 115.2K 800 meters
10 230.4K [1] 400 meters
11 460.8K [1] 200 meters
12 1040K [1] 100 meters
13 2080K [1] 40 meters
14 4160K [1] 20 meters
  1. 1.0 1.1 1.2 1.3 1.4 On Linux systems, stting these bit rates requires code using ioctl() with the TCGETS2 and TCSETS2 parameters.

Connectors

2x RJ45

Both RJ45 ports, and all of our Modbus based devices are designed to be compatible with 2W-MODBUS RJ45 following this pinout:

ModbusRJ45.png

TS-1400 RJ45.png

Product Notes

FCC Advisory

This equipment generates, uses, and can radiate radio frequency energy and if not installed and used properly (that is, in strict accordance with the manufacturer's instructions), may cause interference to radio and television reception. It has been type tested and found to comply with the limits for a Class A digital device in accordance with the specifications in Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the owner will be required to correct the interference at his own expense.

If this equipment does cause interference, which can be determined by turning the unit on and off, the user is encouraged to try the following measures to correct the interference:

Reorient the receiving antenna. Relocate the unit with respect to the receiver. Plug the unit into a different outlet so that the unit and receiver are on different branch circuits. Ensure that mounting screws and connector attachment screws are tightly secured. Ensure that good quality, shielded, and grounded cables are used for all data communications. If necessary, the user should consult the dealer or an experienced radio/television technician for additional suggestions. The following booklets prepared by the Federal Communications Commission (FCC) may also prove helpful:

How to Identify and Resolve Radio-TV Interference Problems (Stock No. 004-000-000345-4) Interface Handbook (Stock No. 004-000-004505-7) These booklets may be purchased from the Superintendent of Documents, U.S. Government Printing Office, Washington, DC 20402.

Limited Warranty

See our Terms and Conditions for more details.